The T&P relief valve: testing, leaks and rules

The temperature and pressure (T&P) relief valve is the safety valve that keeps a tank from overheating or overpressurizing. It should almost never open, so a drip from it is a message about your system.

As an Amazon Associate we earn from qualifying purchases. How this site earns. We have not tested these products; see how we choose.

Updated October 29, 2026Research based, not hands-on testing

ENDS ABOVETHE FLOORTEST LEVERT&P VALVETANKGAP
Fig. 1 The T&P valve opens on too much heat or pressure. Its discharge pipe runs down and ends no more than 6 inches above the floor or drain.

Short answer

A T&P valve opens when the tank gets too hot or the pressure too high. Typical home valves, such as Watts’ 10L series, are rated 150 psi and 210 F. If it drips, the cause is usually thermal expansion on a closed system, high house pressure, too high a temperature, or a worn valve. The discharge pipe must end no more than 6 inches above the floor, a floor drain or a waste receptor, with no threads, valves or tees at the end (ICC). Never cap or plug it.

What it does

A T&P valve has a probe that sits in the hottest water near the top of the tank. It opens if water temperature reaches its set point or pressure reaches its rating. Watts’ 10L valve, a common example, lists 210 F temperature relief and a 150 psi pressure setting (Watts). Model numbers matter: some valves are set differently, so replace like with like.

Discharge pipe rules

The ICC’s CodeNotes on water heater safety summarizes the International Plumbing and Residential Code rules for the pipe from the valve (ICC). Among them:

ENDS ABOVETHE FLOORTEST LEVERT&P VALVETANKGAP
Fig. 2 The discharge pipe runs full length down beside the tank and stops just above the floor, unthreaded, so any discharge is visible and safe.

When it drips: what to check

Dripping T&P valve: causes and fixes

CauseHow to tellFix
Thermal expansionDrips after the heater runs, on a system with a PRV, check valve or backflow preventerAdd or recharge an expansion tank
High house pressureA gauge on a hose bib reads well above normalHave the pressure reducing valve checked or adjusted
Temperature too highWater at the tap is far above 120 FLower the setting
Worn valve or debrisDrips constantly at normal pressure and temperatureReplace the valve

Testing the valve

  1. Put a bucket under the pipe

    The water that comes out is scalding. Keep hands and feet clear of the pipe end.

  2. Lift the test lever

    Raise it for a few seconds. Hot water should flow freely from the discharge pipe.

  3. Let it snap back

    Release the lever. The flow should stop within a moment.

  4. Watch for a drip

    A valve that will not open, or keeps dripping after testing, needs replacing. Old valves that have never been tested sometimes start dripping when first opened.

Replacing a T&P valve

Turn off gas or power, shut the cold supply, open a hot tap, and drain a few gallons from the drain valve so the water level is below the valve. Unscrew the discharge pipe and the old valve, wrap the threads of the matching replacement, screw it in with the outlet facing down, reconnect the pipe, refill the tank with a hot tap open until water runs steadily, then restore heat.

See 3/4 inch T&P relief valves

Questions people ask

Why is my water heater relief valve leaking?

The common causes are thermal expansion in a closed system (no working expansion tank), house water pressure that is too high, a temperature set too high, or a valve with debris on its seat or simply worn out. A.O. Smith also says a dripping T&P valve means it failed or the temperature is set too high.

How do I test a T&P valve?

Put a bucket under the discharge pipe, then lift the test lever for a few seconds so hot water flows, and let it snap back. If it does not flow, or keeps dripping after it closes, replace the valve. Follow your heater’s manual for how often to test.

Can I plug or cap a leaking relief valve?

No, never. The ICC notes the discharge pipe end must not be threaded, precisely so no one caps it. A blocked relief valve can let a tank fail violently.

What T&P valve do I need?

Match the old valve’s pressure and temperature ratings, thread size (usually 3/4 inch) and probe length, and the heater’s BTU or kW rating printed on the valve. The water heater manual lists the required rating.

Sources

  1. Watts, Series 10L temperature and pressure relief valve 150 psi, 210 F (maker)
  2. ICC Building Safety Journal, CodeNotes: Water heater safety in the I-Codes

Last reviewed October 29, 2026. Models, codes and listings change; check your heater’s manual and your local code, and follow the maker’s instructions.